FREQUENTLY ASKED QUESTIONS
ARCRITZ Load Break Tool
Find information about applications, voltage, testing, warranty and maintenance of the Ritz ARCRITZ Load Break Tool.
Materials and Technology
Learn how the internal chamber extinguishes the arc, and about the fiberglass body and ARCRITZ operating cycle counter.
It is a device designed to open a fuse cutout or disconnect switch while the network is energized and under load. The arc generated during opening is extinguished inside the device’s internal chamber, while the operator remains on the ground using an insulated operating pole. The ARCRITZ is Ritz’s load break tool.
RTZ32370
During opening, the internal chamber extinguishes the arc in a controlled manner. Without a suitable load break device, opening a switch under load generates an electrical arc, which is the most serious hazard associated with this operation.
RTZ32370
The body is made of a fiberglass tube, which provides electrical insulation and mechanical strength for operation. Its dry withstand voltage at power frequency is 41 kV.
RTZ32370
The integrated cycle counter records each operation, allowing the maintenance team to monitor wear and schedule servicing based on actual use rather than estimates. The equipment may leave the factory with up to 20 cycles already recorded as a result of functional and quality tests, which is not considered prior use.
RTZ32370
Safety and Performance
Learn how remote operation, performance in harsh environments and periodic inspection contribute to the safe use of ARCRITZ.
The ARCRITZ is operated manually from a safe distance using an insulated operating pole. The operator remains on the ground, outside the hazard zone.
RTZ32370
Yes. The equipment remains operational in environments with high levels of pollution and humidity.
RTZ32370
A complete preventive maintenance service is required every 500 operating cycles and must be performed by Ritz or an authorized service provider. The cycle counter indicates when maintenance is due.
RTZ32370
Standards and Compliance
See how ARCRITZ is tested in accordance with IEC 62271-103, class E1, including mechanical and switching tests.
The ARCRITZ is tested as Class E1 equipment in accordance with IEC 62271-103, which covers switches for alternating current, and is also subjected to mechanical endurance testing.
RTZ32370
The tests cover real-world field conditions: active current (5 operations at 17.0 kV and 900 A), parallel transformer switching (10 operations at 3.7 kV and 900 A), magnetizing current (12 operations at 18.7 kV and 6 A), no-load cable switching (12 operations at 20.0 kV and 16 A), no-load line switching (12 operations at 20.0 kV and 1.5 A), and capacitor bank switching (12 operations at 22.0 kV and 53 A).
RTZ32370
A static load test of 227 kg and 2,000 no-load operating cycles.
RTZ32370
Specifications and Applications
Check ARCRITZ voltage and current ratings, applications and compatibility for operating fuse cutouts and disconnect switches on overhead networks.
Fuse cutouts on transformers and circuit sections, as well as knife-blade disconnect switches on energized single-phase or three-phase overhead distribution networks, during preventive and corrective maintenance.
RTZ32370
The ARCRITZ is designed for overhead distribution networks up to 25 kV, with a maximum rated voltage of 27 kV. Its interrupting current is 600 A, and its rated current is 900 A.
RTZ32370
It can be used on single-phase or three-phase networks with resistive, highly capacitive, or highly inductive circuits.
RTZ32370
Commercial and Logistics
Find information about warranty, country of manufacture, and how to request a quotation and technical datasheet for ARCRITZ.
The warranty is 2 years or 1,000 operating cycles, whichever comes first.
RTZ32370
Yes. ARCRITZ is manufactured in Brazil by Ritz Ferramentas, which has designed and manufactured tools for energized and de-energized power systems for 60 years.
RTZ32370
Use the quote form on the product page or contact the Ritz team at +55 31 2125 4000. Send your system voltage, the device you need to operate, the quantity and the destination country
RTZ32370
Need help specifying the right ARCRITZ for your network?
Contact the Ritz team to confirm the voltage, compatibility with your switches and supply requirements.